Wuxi Security Monitoring System Inspection Item Requirements and Test Methods

Your current location: home page >> technical support >> Solution

Wuxi Security Monitoring System Inspection Item Requirements and Test Methods

Date of issue: 2021-03-05 Author: Wuxi Dehang Technology Co., Ltd Click:

1、 System control function inspection

a. Editing function inspection: manual or automatic programming can be realized by controlling the device keyboard to achieve fixed or sequential display and switching of all video images on the designated display.

b. Remote control function inspection: the control equipment shall control all front controlled parts such as PTZ, lens and protective cover stably and accurately.

2、 Monitoring function inspection

a. The monitoring area shall meet the design requirements. The illuminance in the monitoring area shall meet the design requirements. If not, check whether there is an auxiliary light source.

b. For key parts that must be monitored in the design, check whether real-time monitoring is realized and there is no blind area.

3、 Display function inspection

a. The images displayed in single or multiple images shall be clear and stable;

b. The monitoring screen shall display the date, time and front end of the monitored screen video camera No. or address code of;

c. It shall have the functions of picture freeze, switching display, multi-channel alarm display, arbitrary setting of video alert area, etc;

d. The image display quality shall meet the design requirements, and the image quality shall be scored at level 5 according to the current national standard Technical Code for Civil Closed Circuit Surveillance Television System Engineering (GB 50198).


 Wuxi Security Monitoring


4、 Record function inspection

a. The images taken by the front-end camera shall be recorded according to the design requirements, and the images required to be recorded in the design shall be continuous and stable;

b. Record date, time and the number or address code of the front camera of the monitored image shall be displayed on the record screen;

c. It shall have storage function. In case of power failure or shutdown, all programming settings, camera number, time, address, etc. can be stored. Once power supply is restored, the system shall automatically enter into normal working state.

5、 Playback function inspection

a. The playback image shall be clear, and the gray level and resolution shall meet the design requirements;

b. The playback image shall have the date, time and the number or address code of the front camera of the monitored image, which shall be clear and accurate;

c. When the recorded image is the image recorded by the alarm linkage, the playback image shall ensure the coverage of the camera at the alarm scene, so that the playback image can reproduce the alarm scene;

d. There should be no obvious deterioration between the playback image and the monitoring image, and the playback effect of the moving target image should meet the design and use requirements.

6、 Alarm linkage function inspection

a. When an alarm occurs in the intrusion alarm system, the linkage device shall automatically turn on the corresponding equipment. The alarm scene screen shall be able to display on the designated monitor, the camera address code and time shall be displayed, and the alarm screen shall be recorded in a single screen;

b. When linked with intrusion detection system and access control system, it shall be able to accurately trigger the linked equipment;

c. The alarm linkage function of other systems shall meet the design requirements.

6、 The image loss alarm function detects that when the video input signal is lost, an alarm can be sent.

7、 Other functional items shall be inspected for items that are included in the specific project but not involved in the above functions, and the inspection requirements shall conform to the requirements of corresponding standards, engineering contracts and formal design documents.

Website: //nabenjixie.cn/news/502.html

key word: Wuxi Security Monitoring , Wuxi security monitoring manufacturer , Which one is good for Wuxi security monitoring

Recent browsing:

  • Online Service
  • contact number
    thirteen billion eight hundred and sixty-one million eight hundred and thirty-two thousand two hundred and thirty-seven
  • Online Message
  • Mobile website
  • Online consultation
    Welcome to leave us a message
    Please enter your message here, and we will contact you as soon as possible.
    full name
    contacts
    Telephone
    Landline/mobile number
    mailbox
    mailbox
    address
    address